1 year agoand it gets nowhere near those thresholds, the voltage fluctuates in the 224-234 range.
I’m assuming you measured hot to neutral, and didn’t find any transients.
Did you put your oscilloscope on hot to ground as well? A faulty ground could cause what you are seeing.
Do you have any CFL bulbs anywhere in your house? I once had a dead CFL bulb in a fixture in my basement. Anytime I turned on my basement light, every LED lamp in the house would strobe.
Just for shits and grind, how about neutral to ground? They should be bonded together in the breaker box (and nowhere else), but if there is a fault, you might see some significant potential across them.
You’ve tried different outlets?